| This section does not cite any references or sources. (June 2013) |
An electrical "3G" power cable
found commonly in modern European houses. The cable consists of 3 wires
(2 wires + 1 grounding in case if cable has "3G" name) and is
double-insulated.
Many electrical codes now recognise (or even require) the use of wire covered with green insulation, additionally marked with a prominent yellow stripe, for safety earthing (grounding) connections. This growing international standard was adopted for its distinctive appearance, to reduce the likelihood of dangerous confusion of safety earthing (grounding) wires with other electrical functions, especially by persons affected by red-green colour blindness.
The down side of the use of International colours is that, in the UK for example, phases could be identified as being live by using coloured indicator lights: red, yellow and blue. The new cable colours of brown, black and grey do not lend themselves to coloured indicators. For this reason, three-phase control panels will often use indicator lights of the old colours.[citation needed][clarification needed]
| Standard wire colours for flexible cable (e.g. Extension cords, power (line) cords and lamp cords) |
|||
|---|---|---|---|
| Region or Country | Phases | Neutral | Protective earth/ground |
| European Union (EU), Argentina, Australia, South Africa (IEC 60446) | |||
| Australia, New Zealand (AS/NZS 3000:2007 3.8.3) | |||
| Brazil | |||
| United States, Canada | |||
| Standard wire colours for fixed cable (e.g. In-, On- or Behind-the-wall wiring cables) |
|||
| Region or Country | Phases | Neutral | Protective earth/ground |
| Argentina | |||
| European Union (EU) (IEC 60446) including UK from 31 March 2004 (BS 7671) | |||
| UK prior to 31 March 2004 (BS 7671) | |||
| Australia, New Zealand (AS/NZS 3000:2007 clause 3.8.1, table 3.4) | Any colours other than Recommended for single phase: Recommended for multiphase: |
||
| Brazil | |||
| South Africa | |||
| India, Pakistan | |||
| United States | (brass) |
||
| Canada | |||
| Notes:
Parenthesised colours in italics are used on metallic terminals. "Green/yellow" means green with yellow stripe. See illustrations nearby. The colours in this table represent the most common and preferred standard colours for wiring; however others may be in use, especially in older installations. Australian and New Zealand wiring standards allow both European and Australian colour codes. Australian-standard phase colours conflict with IEC 60446 colours, where IEC-60446 supported neutral colour (blue) is an allowed phase colour in the Australia/New Zealand standard. Care must be taken when determining system used in existing wiring. Canadian and American wiring practices are very similar, with ongoing harmonisation efforts. |
|||
Wiring methods
Installing electrical wiring by "chasing" grooves into the masonry structure of the walls of a building
- Intended use and amount of power demand on the circuit
- Type of occupancy and size of the building
- National and local regulations
- Environment in which the wiring must operate.
Wires and cables are rated by the circuit voltage, temperature rating and environmental conditions (moisture, sunlight, oil, chemicals) in which they can be used. A wire or cable has a voltage (to neutral) rating and a maximum conductor surface temperature rating. The amount of current a cable or wire can safely carry depends on the installation conditions.
Early wiring methods
The first interior power wiring systems used conductors that were bare or covered with cloth, which were secured by staples to the framing of the building or on running boards. Where conductors went through walls, they were protected with cloth tape. Splices were done similarly to telegraph connections, and soldered for security. Underground conductors were insulated with wrappings of cloth tape soaked in pitch, and laid in wooden troughs which were then buried. Such wiring systems were unsatisfactory because of the danger of electrocution and fire, plus the high labour cost for such installations.Knob and tube
Main article: Knob and tube wiring
Knob-and-tube wiring (the orange cable is an unrelated extension cord)
By the 1940s, the labour cost of installing two conductors rather than one cable resulted in a decline in new knob-and-tube installations. However, the US code still allows new K&T wiring installations in special situations (some rural and industrial applications).
Metal-sheathed wires
In the United Kingdom, an early form of insulated cable,[1] introduced in 1896, consisted of two impregnated-paper-insulated conductors in an overall lead sheath. Joints were soldered, and special fittings were used for lamp holders and switches. These cables were similar to underground telegraph and telephone cables of the time. Paper-insulated cables proved unsuitable for interior wiring installations because very careful workmanship was required on the lead sheaths to ensure moisture did not affect the insulation.A system later invented in the UK in 1908 employed vulcanised-rubber insulated wire enclosed in a strip metal sheath. The metal sheath was bonded to each metal wiring device to ensure earthing continuity.
A system developed in Germany called "Kuhlo wire" used one, two, or three rubber-insulated wires in a brass or lead-coated iron sheet tube, with a crimped seam. The enclosure could also be used as a return conductor. Kuhlo wire could be run exposed on surfaces and painted, or embedded in plaster. Special outlet and junction boxes were made for lamps and switches, made either of porcelain or sheet steel. The crimped seam was not considered as watertight as the Stannos wire used in England, which had a soldered sheath.[2]
A somewhat similar system called "concentric wiring" was introduced in the United States around 1905. In this system, an insulated electrical wire was wrapped with copper tape which was then soldered, forming the grounded (return) conductor of the wiring system. The bare metal sheath, at earth potential, was considered safe to touch. While companies such as General Electric manufactured fittings for the system and a few buildings were wired with it, it was never adopted into the US National Electrical Code. Drawbacks of the system were that special fittings were required, and that any defect in the connection of the sheath would result in the sheath becoming energised.[3]
Other historical wiring methods
Other methods of securing wiring that are now obsolete include:- Re-use of existing gas pipes when converting gas light installations to electric lighting. Insulated conductors were pulled through the pipes that had formerly supplied the gas lamps. Although used occasionally, this method risked insulation damage from sharp edges inside the pipe at each joint.
- Wood mouldings with grooves cut for single conductor wires, covered by a wooden cap strip. These were prohibited in North American electrical codes by 1928. Wooden moulding was also used to some degree in England, but was never permitted by German and Austrian rules.[4]
- A system of flexible twin cords supported by glass or porcelain buttons was used near the turn of the 20th century in Europe, but was soon replaced by other methods.[5]
- During the first years of the 20th century, various patented forms of wiring system such as Bergman and Peschel tubing were used to protect wiring; these used very thin fiber tubes, or metal tubes which were also used as return conductors.[6]
- In Austria, wires were concealed by embedding a rubber tube in a groove in the wall, plastering over it, then removing the tube and pulling wires through the cavity.[7]
Cables
Main article: Power cable
Wiring for extremely wet conditions
The first rubber-insulated cables for building wiring were introduced in 1922 with US patent 1458803, Burley, Harry & Rooney, Henry, "Insulated electric wire", issued 1923-06-12, assigned to Boston Insulated Wire And Cable.[citation needed] These were two or more solid copper electrical wires with rubber insulation, plus woven cotton cloth over each conductor for protection of the insulation, with an overall woven jacket, usually impregnated with tar as a protection from moisture. Waxed paper was used as a filler and separator.
Over time, rubber-insulated cables become brittle because of exposure to atmospheric oxygen, so they must be handled with care and are usually replaced during renovations. When switches, socket outlets or light fixtures are replaced, the mere act of tightening connections may cause hardened insulation to flake off the conductors. Rubber insulation further inside the cable often is in better condition than the insulation exposed at connections, due to reduced exposure to oxygen.
The sulphur in vulcanised rubber insulation attacked bare copper wire so the conductors were tinned to prevent this. The conductors reverted to being bare when rubber ceased to be used.
Diagram of a simple electrical cable with three insulated conductors
The simplest form of cable has two insulated conductors twisted together to form a unit. Such un-jacketed cables with two (or more) conductors are used only for extra low voltage signal and control applications such as doorbell wiring.
US single-phase residential power distribution transformer, showing the
two insulated "Line" conductors and the bare "Neutral" conductor
(derived from the earthed center-tap of the transformer). The
distribution supporting centenaries are also shown.
Copper conductors
Main article: Copper wire and cable
Electrical devices often contain copper conductors because of their multiple beneficial properties, including their high electrical conductivity, tensile strength, ductility, creep resistance, corrosion resistance, thermal conductivity, coefficient of thermal expansion, solderability, resistance to electrical overloads, compatibility with electrical insulators and ease of installation.Despite competition from other materials, copper remains the preferred electrical conductor in nearly all categories of electrical wiring.[9][10] For example, copper is used to conduct electricity in high, medium and low voltage power networks, including power generation, power transmission, power distribution, telecommunications, electronics circuitry, data processing, instrumentation, appliances, entertainment systems, motors, transformers, heavy industrial machinery and countless other types of electrical equipment.[11]
Aluminium conductors
Terminal blocks for joining aluminium and copper conductors. The terminal blocks may be mounted on a DIN rail.
Aluminium conductors were originally indiscriminately used with wiring devices intended for copper conductors. This practice was found to cause defective connections unless the aluminium was one of a special alloy, or all devices—breakers, switches, receptacles, splice connectors, wire nuts, etc.—were specially designed for the purpose. These special designs address problems with junctions between dissimilar metals, oxidation on metal surfaces and mechanical effects that occur as different metals expand at different rates with increases in temperature.
Unlike copper, aluminium has a tendency to cold-flow under pressure, so screw clamped connections may get loose over time. This can be mitigated by using spring-loaded connectors that apply constant pressure, applying high pressure cold joints in splices and termination fittings, or using a bolted mechanical type clamp wire connector and tightening it to a specified torque.
Also unlike copper, aluminium forms an insulating oxide layer on the surface. This is sometimes addressed by coating aluminium conductors with an antioxidant paste at joints, or by applying a mechanical termination designed to break through the oxide layer during installation.
Because of improper design and installation, some junctions to wiring devices would overheat under heavy current load, and cause fires. Revised standards for wiring devices (such as the CO/ALR "copper-aluminium-revised" designation) were developed to reduce these problems. Nonetheless, aluminium wiring for residential use has acquired a poor reputation and has fallen out of favour.
Aluminium conductors are still used for bulk power distribution and large feeder circuits, because they cost less than copper wiring, and weigh less, especially in the large sizes needed for heavy current loads. Aluminium conductors must be installed with compatible connectors.
Modern wiring materials
Modern non-metallic sheathed cables, such as (US and Canadian) Types NMB and NMC, consist of two to four wires covered with thermoplastic insulation, plus a bare wire for grounding (bonding), surrounded by a flexible plastic jacket. Some versions wrap the individual conductors in paper before the plastic jacket is applied.Special versions of non-metallic sheathed cables, such as US Type UF, are designed for direct underground burial (often with separate mechanical protection) or exterior use where exposure to ultraviolet radiation (UV) is a possibility. These cables differ in having a moisture-resistant construction, lacking paper or other absorbent fillers, and being formulated for UV resistance.
Rubber-like synthetic polymer insulation is used in industrial cables and power cables installed underground because of its superior moisture resistance.
Insulated cables are rated by their allowable operating voltage and their maximum operating temperature at the conductor surface. A cable may carry multiple usage ratings for applications, for example, one rating for dry installations and another when exposed to moisture or oil.
Generally, single conductor building wire in small sizes is solid wire, since the wiring is not required to be very flexible. Building wire conductors larger than 10 AWG (or about 6 mm²) are stranded for flexibility during installation, but are not sufficiently pliable to use as appliance cord.
Cables for industrial, commercial and apartment buildings may contain many insulated conductors in an overall jacket, with helical tape steel or aluminium armour, or steel wire armour, and perhaps as well an overall PVC or lead jacket for protection from moisture and physical damage. Cables intended for very flexible service or in marine applications may be protected by woven bronze wires. Power or communications cables (e.g., computer networking) that are routed in or through air-handling spaces (plenums) of office buildings are required under the model building code to be either encased in metal conduit, or rated for low flame and smoke production.
Mineral insulated cables at a panel board
Because multiple conductors bundled in a cable cannot dissipate heat as easily as single insulated conductors, those circuits are always rated at a lower "ampacity". Tables in electrical safety codes give the maximum allowable current for a particular size of conductor, for the voltage and temperature rating at the surface of the conductor for a given physical environment, including the insulation type and thickness. The allowable current will be different for wet or dry, for hot (attic) or cool (underground) locations. In a run of cable through several areas, the most severe area will determine the appropriate rating of the overall run.
Cables usually are secured by special fittings where they enter electrical apparatus; this may be a simple screw clamp for jacketed cables in a dry location, or a polymer-gasketed cable connector that mechanically engages the armour of an armoured cable and provides a water-resistant connection. Special cable fittings may be applied to prevent explosive gases from flowing in the interior of jacketed cables, where the cable passes through areas where inflammable gases are present. To prevent loosening of the connections of individual conductors of a cable, cables must be supported near their entrance to devices and at regular intervals through their length. In tall buildings, special designs are required to support the conductors of vertical runs of cable. Usually, only one cable per fitting is allowed unless the fitting is otherwise rated.
Special cable constructions and termination techniques are required for cables installed in ocean-going vessels; in addition to electrical safety and fire safety, such cables may also be required to be pressure-resistant where they penetrate bulkheads of a ship. Resistance to corrosion caused by salt water or salt spray is also required.
Raceways
See also: Electrical conduit
Electrical conduit risers, seen inside fire-resistance rated shaft, as seen entering bottom of a firestop. The firestop is made of firestop mortar on top, rockwool on the bottom. Raceways are used to protect cables from damage.
Where wiring, or raceways that hold the wiring, must traverse fire-resistance rated walls and floors, the openings are required by local building codes to be firestopped. In cases where safety-critical wiring must be kept operational during an accidental fire, fireproofing must be applied to maintain circuit integrity in a manner to comply with a product's certification listing. The nature and thickness of any passive fire protection materials used in conjunction with wiring and raceways has a quantifiable impact upon the ampacity derating, because the thermal insulation properties needed for fire resistance also inhibit air cooling of power conductors.
A cable tray can be used in stores and dwellings
Since wires run in conduits or underground cannot dissipate heat as easily as in open air, and since adjacent circuits contribute induced currents, wiring regulations give rules to establish the current capacity (ampacity).
Special sealed fittings are used for wiring routed through potentially explosive atmospheres.
Bus bars, bus duct, cable bus
Main article: Bus bar
Topside of firestop with penetrants consisting of electrical conduit on the left and a bus duct on the right. The firestop consists of firestop mortar on top and rockwool on the bottom, for a 2 hour fire-resistance rating.
In industrial applications, conductor bars are often pre-assembled with insulators in grounded enclosures. This assembly, known as bus duct or busway, can be used for connections to large switchgear or for bringing the main power feed into a building. A form of bus duct known as "plug-in bus" is used to distribute power down the length of a building; it is constructed to allow tap-off switches or motor controllers to be installed at designated places along the bus. The big advantage of this scheme is the ability to remove or add a branch circuit without removing voltage from the whole duct.
Busbars for distributing PE (ground)
For very large currents in generating stations or substations, where it is difficult to provide circuit protection, an isolated-phase bus is used. Each phase of the circuit is run in a separate grounded metal enclosure. The only fault possible is a phase-to-ground fault, since the enclosures are separated. This type of bus can be rated up to 50,000 amperes and up to hundreds of kilovolts (during normal service, not just for faults), but is not used for building wiring in the conventional sense.
Electrical panels
Electrical panels, cables and firestops in an electrical service room at a paper mill in Ontario, Canada
Degradation by pests
Rasberry crazy ants have been known to consume the insides of electrical wiring installations, preferring DC over AC currents. This behaviour is not well understood by scientists.[12]Squirrels, rats and other rodents may gnaw on unprotected wiring, causing fire and shock hazards.[13][14]
See also
- 10603 – a frequently used MIL-SPEC compliant wire
- Cable
- Cable Entry System
- Cable tray
- Domestic AC power plugs and sockets
- Electrical conduit
- Electrical room
- Electrical wiring in North America
- Electrical wiring in the United Kingdom
- Electricity distribution
- Grounding
- Home wiring
- Industrial and multiphase power plugs and sockets
- MIL-DTL-13486 – MIL-SPEC compliant wire
- Neutral wire
- OFHC
- Portable cord
- Restriction of Hazardous Substances Directive (RoHS)
- Single-phase electric power
- Structured cabling
- Three-phase electric power
References
- University of Illinois Extension. "Tree Squirrels > Damage Prevention and Control Measures". Living with Wildlife in Illinois. University of Illinois Board of Trustees. Retrieved 12 March 2013.
Bibliography
- Croft, Terrel (1915) Wiring of Finished Buildings, McGraw Hill, New York.
Further reading
- National Electrical Code — Basis of most US electrical codes. Choose NFPA 70 (general purpose) or NFPA 70A (one and two family dwellings). Free registration required.
- National Electrical Code 2011 (2011 ed.), Quincy MA: National Fire Protection Association, 2010. — periodically re-issued every 3 years
- NEMA comparison of IEC 60364 with the US NEC[dead link]
- Cauldwell, Rex (2002). Wiring a House (For Pros By Pros). Newtown, CT, USA: Taunton Press. ISBN 1-56158-527-0.
- Hirst, E. Electric Utilities and Energy
- Litchfield, Michael; Michael McAlister (2008). Taunton's wiring complete : expert advice from start to finish (Revised ed.). Newtown, CT: Taunton Press. ISBN 978-1-60085-256-5.
No comments:
Post a Comment